Horner-apg XL7 OCS User Manual Page 87

  • Download
  • Add to my manuals
  • Print
  • Page
    / 110
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 86
XL7 User Manual
The Output State On Controller Stop group box contains items to allow the user to specify how the
remaining digital outputs behave when the controller is stopped. These items can either hold their value
or default to some value when the controller is stopped.
15.7 Analog Input Configuration
The following figure illustrates the Analog Input Configuration dialog.
Figure 15.5 – Analog Input Configuration Dialog
The Channel x drop down windows allow the user to specify the mode for each analog input to operate.
The Channel x drop down windows are enabled/disabled according to which model is being configured.
All of the models have the following modes available:
- 0..10V
- 0..20mA
- 4..20mA
On model 005, all channels (1-4) also have the following modes available:
- 100mV
- PT100 DIN RTD, 1/20°c
- Type J Thermocouple, 1/20°c
- Type K Thermocouple, 1/20°c
- Type N Thermocouple, 1/20°c
- Type T Thermocouple, 1/20°c
- Type E Thermocouple, 1/20°c
- Type R Thermocouple, 1/20°c
- Type S Thermocouple, 1/20°c
- Type B Thermocouple, 1/20°c
The Filter Constant provides filtering to all channels.
Page 87 of 110
Page view 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 109 110

Comments to this Manuals

No comments